Screw Type Central Air Conditioning Maintenance and Self-Check a Trick

Screw Type Central Air Conditioning Maintenance and Self-Check a Trick

First, overhaul and maintenance project classification

(A) System maintenance:

1, air conditioner, fan coil maintenance; 2, air conditioning main unit maintenance;

3, terminal equipment maintenance service;

4, air conditioning cooling tower maintenance service.

  • Cleaning:

1, refrigeration unit, cooling tower, hot and cold water system, air conditioning system, circulating water system;

2, heat exchange equipment, condenser, evaporator, cooling water system, refrigerant water system in the cold unit;

3, fan coil surface cooler, condensate pipeline equipment.

  • Maintenance:

1, air conditioner, fan coil maintenance;

2, host system: compressor, vacuum valve, sight mirror, shield pump, real pump, heat transfer tube, condenser, evaporator, automatic control element;

3, cooling tower: fan, bearing, water distributor, filter, film material, tower parts, etc Two, maintenance cycle

  • Daily repair and maintenance
timepositionInspection itemscorrect value
    Before startup1. Oil heaterCheck if the electric heater is powered on when stoppingTurn on the electric heater
2. Oil separator sight glassCheck the oil levelEnsure that the oil level is above 1/3 of the sight glass
Manual shut-off valve on the spray pipeCheck if the valve is fully openOpen the valve
4 Power Supply VoltageCheck with a voltmeterNot exceeding ± 10% of the rated value
5 Environmental temperature (outdoor temperature)Check the thermometer40
  Start upMirror covered on one sideCheck the rotation of the star wheelConnect according to EY302947 normally
Electromagnetic valve on spray pipe 2Check if it is turned on at startup 
3 Vibration and noiseFeeling and listeningNo abnormal vibration or noise
       function1. Oil separator sight glassCheck the oil levelSupplement refrigeration oil*
Mirror with two side coversCheck if there is fuel injection 
3 Exhaust pressureCheck the high-pressure gauge (exhaust)1.1~1.8MPa
4. Inhalation pressureCheck the low pressure gauge (suction)0.30.6MPa
5 suction pressure differenceCheck the low pressure gauge (suction)0.05MPa
1. Hot water outlet temperature (during heating)Check the thermometer30~45
2. Temperature of chilled water outlet (during refrigeration)Check the thermometer5~10
3. High and low pressure differenceCheck the high-pressure gauge (exhaust)0.1MPa
 Every season1. Refrigerant injection amountCheck the liquid microscopePipeline liquid without bubbles
2. Lubricating oil injection amountCheck the oil level gaugeWithin the prescribed scope
  • body maintenance cycle
Screw Type Central Air Conditioning Maintenance and Self-Check a Trick1

Note: △ Inspection or cleaning, ○ replacement According to the maintenance  cycle  of the above table, when it is necessary to replace the air conditioning piston ring or bearing, it should be implemented by the technical personnel approved by the compressor manufacturer or sent by the compressor manufacturer to assist the service.

Three, maintenance key projects

  • Power supply and control part

1, the working power supply of the unit is 3N~, AC380V, 50Hz. Need to check the electric control cabinet in the power supply part and control part of the abnormal and fixed terminals, including the total power wiring copper bar, automatic air circuit breaker (air switch), δ-δor Y-δcompressor start electrical device, PLC touch screen, target flow switch, freezing, cooling water pump linkage control line (control contact  for passive contact), temperature sensor, freezing, cooling water pump, Cooling tower linkage control line (control contact is passive contact), electronic control instrument and so on nodes.

2, check the power supply  voltage: the maximum allowable phase voltage  imbalance is 2%, and the phase current  imbalance is 10%. Phase voltage imbalance is greater than 2%, absolutely can not be turned on.

For example: the nominal voltage is 3N~, AC380V, 50Hz, measured UAB=376V, UAC=379V, UBC=385V. Get the average voltage = (376+379+385) /3= 380V: Determine the deviation from the average voltage:

△UAB=380-376=4V, △UAC=380-379=1V, △UBC=385-380=5V, the maximum deviation value is 5V, 5/380=1.3%, the maximum phase voltage unbalance is 1.3%.

Please inform the user that the damage caused by startup operation when the phase voltage unbalance is greater than 2% is regarded as improper operation and is not covered by the warranty of this product.

  • Operation and appearance of the system (leakage, damage)
  1. Confirm that the system is not leaked.
  • Check that the sequence of actions is normal.

3, check whether the compressor wiring is correct or loose.

4. Measure whether the working current of each compressor is normal.

5, check whether it is correctly installed, and confirm that the flow switch and the control cabinet have been correctly connected.

6, point chilled water, cooling water pump and cooling tower fan, check the motor phase sequence.

7. Check whether the coil of the compressor capacitive solenoid valve is locked, and whether the capacitive capillary is damaged.

8, check the water side of the pressure gauge and thermometer connection is correct, flow switch is normal.

9, check whether the oil level in the compressor is normal, the normal compressor oil level is generally in the middle of the sight mirror.

10, all the system (condenser outlet Angle valve, compressor suction, exhaust stop valve, etc.) in the open state.

11. Check whether the high and low pressure Settings of the pressure relay are normal (high pressure is set to 1.8MPa, low pressure 0.2MPa).

12, check whether the cooling tower/expansion tank water supply device is smooth, whether the automatic exhaust valve can automatically exhaust.

13, confirm whether the unit has abnormal noise. There is no contact, collision or friction between pipes and pipes to protect and clean.

14, check the frame and other metal shell such as rust, with coarse sandpaper and cloth to wipe rust spots apply anti-rust paint.

15, adjust the water flow and check whether the water pressure drop through the evaporator and condenser meets the requirements of the normal operation of the unit. That is, the inlet and outlet pressure of the chilled water and the inlet and outlet pressure of the cooling water of the unit should be guaranteed at least 0.2MPa

  • The use of lubricating oil specifications and precautions

1, lubricating oil with lubrication, cooling, sealing, driving hydraulic cylinder and other functions. It has a decisive impact on the performance of the screw compressor, if used improperly or incorrectly, it will lead to serious damage to the compressor body. Therefore, the internal lubricating oil system is the key to the normal operation of the compressor, but the performance of the oil changes with time, and there is a relatively stable period of time when the performance will be sharply deteriorated. Therefore, the oil should be changed at the right time.

Screw Type Central Air Conditioning Maintenance and Self-Check a Trick2

2, when should replace the lubricating oil to ensure the normal operation of the compressor, can be in accordance with the following methods:

  • Time set replacement: generally every 10,000 hours to check or replace the lubricating oil, and after the first operation, the air cooling and dry unit with screw compressor 1000 hours recommended to replace the lubricating oil and clean the oil filter. Because the residue of the system assembly will accumulate to the compressor after the formal operation. Therefore, for air-cooled and dry units with screw compressors 1000 hours (cumulative 2 months) should be replaced once, and then according to the cleanliness of the system to replace regularly, if the cleanliness of the system is good, you can replace once every 10,000 hours (or annually).
  • If the exhaust temperature of the compressor is maintained at high temperature and high pressure for a long time, the deterioration of the lubricating oil is accelerated. It is necessary to check the chemical characteristics of the lubricating oil regularly (every 2 months), and replace it when it is unqualified. If it can not be checked regularly, it can be performed according to the following suggestion table.

The operation period is based on 16 hours of operation per day

running staterefrigerationHeating at 45 Heating at 50 Heating at 55 Heating above 55 
Replacement time (hours)10000800040001500500
Replacement time (number of operating months) 20 16 8 3 1

3, the acidification of lubricating oil, will directly affect the life of the compressor motor, so it should be regularly checked whether the acidity of lubricating oil is qualified, the general acidity of lubricating oil below PH6 must be replaced. If the acidity can not be checked, the dryer filter element of the system should be replaced regularly, so that the dryness of the system is maintained in a dry state.

4. The replacement procedure of lubricating oil needs to consult the compressor manufacturer after sale. In particular, the system has a motor burn precedent, after replacing the motor, it should track the lubricating oil condition every month, or replace the lubricating oil regularly (200 hours), until the system is clean, otherwise the residual acidic components in the system will destroy the motor insulation.

User's notice: Each manufacturer's compressor lubricating oil brand is different, please pay attention to the lubricating oil brand and dosage indicated on the original compressor nameplate when replacing the lubricating oil. Special attention: Because different types of lubricating oil contain anti-rust, anti-oxidation, anti-foam, anti-abrasion and other components are different, do not mix different types and different brands of oil, so as to avoid chemical reaction. Sticky deposits can clog the oil system. If the user replaces it privately, it shall be regarded as improper operation and not covered by the warranty of the product.

(4) Water quality management of circulating water (chilled water, cooling water)

The poor water quality of chilled water and cooling water will not only scale in the heat transfer pipe, affect the heat exchange efficiency, reduce the performance of the unit, but also corrode the heat transfer pipe resulting in major failures of the unit. Customers should be in accordance with the requirements of GB50050-1995 "Industrial circulating cooling water treatment design code" for water quality treatment. When the chilled water system is a closed system, soft water should be used. The cooling water (chilled

water of the open system) should be sampled and analyzed regularly during the operation of the unit, and the water quality should meet the requirements of Table 3-3. If it does not meet the requirements, water quality treatment should be carried out.

User notice: due to water untreated or improper treatment caused by corrosion, erosion or unit performance decline;

Four, maintenance methods and steps

(1) Oil change and filter dryer (must)

1. Preparation: Check whether the compressor lubricating oil is preheated for more than 8 hours. Before the test run, the oil heater should be energized for at least 8 hours to prevent frothing of frozen oil when starting. If the ambient temperature is low, the oil heating time needs to be relatively longer. When starting at low temperature, due to the large viscosity of lubricating oil, it will be difficult to start  and the compressor will not be able to load and unload. Generally, the minimum temperature of the lubricating oil needs to reach 23℃ or more before it can be operated, started, started, recorded operating parameters to analyze the problems existing before and now. Make good preparations.

Short-circuit the high-low differential switch (Figure 1). (It is best not to adjust the differential pressure switch, and the two wires can be short-connected directly.) Run the machine at full load (100%). Close the corner valve (Figure 2). (Pay special attention to restore differential pressure switch after refrigerant recovery)

Screw Type Central Air Conditioning Maintenance and Self-Check a Trick3
  • Press the emergency switch or turn off the power when the low pressure pressure of the machine is less than 0.1MP. Since there is a check valve at the exhaust port of the compressor (Figure 1), the refrigerant will not return to the press, but sometimes the check valve may be closed loosely, so it isbest to close the stop valve of the press exhaust while pressing the emergency switch (Figure 3).
Screw Type Central Air Conditioning Maintenance and Self-Check a Trick4

2, when the above work is completed, turn off the main power supply. Carry on the following process

  • Oil, frozen oil in the system under the pressure of refrigerant gas spray speed  quickly pay attention to health do not spray

Splash to the outside. Drain refrigerant while draining oil, open high pressure gauge stop valve (Figure 4)

  • Clean the oil tank and oil filter (Figure 5) Open the cover of the oil tank and clean the dirty oil tank gauze with dry gauze. Then pour the spent frozen oil into the fine gauze. Remove the two magnets in the oil tank and clean them before putting them back into the oil tank. Use a big wrench to disassemble the oil filter and clean it with waste oil.
Screw Type Central Air Conditioning Maintenance and Self-Check a Trick5

Replace the refrigerant filter A, the refrigerant filter core has 3 in the replacement speed should be fast, to prevent too long contact time with the air adsorption of too much water. B, the filter is packaged in cans, pay attention to protection during transportation, once the packaging is damaged, it is scrapped.

Screw Type Central Air Conditioning Maintenance and Self-Check a Trick6

3, vacuum refueling according to the compressor structure is best from the high pressure side of the refueling. Because the high pressure and low pressure chamber of the compressor are not directly connected, it is difficult to return to the oil tank from the low pressure refueling. Generally, we use the way of vacuuming to evacuate the oil from the low pressure side and inhale the oil from the high pressure side.

About vacuuming. The purpose is to pump out the moisture and air in the system. When the vacuum pump is sealed or aging is more serious, the vacuum degree can not meet the requirements, then it is useless to evacuate such a vacuum pump for a long time)

About vacuum damage. When evacuated to the negative pressure, open the Angle valve to release a little refrigerant from the condenser, which will destroy the vacuum of the system

Note: Liquid supply solenoid valve, because the solenoid valve is also closed when the machine is closed, so when the refrigerant oil is added, the pressure difference switch is restored. Turn on the power to preheat and power on the solenoid valve (can be connected to the oil heater)

Fill the blind tube with oil: fill the blind tube with oil after filtering the replaced old refrigerant oil.

4, preheating: power on preheating at least the oil heating to 23℃ or more to run the boot operation.

  • Open the condenser to clean, clean the system of debris, welding slag, dust, some anti-rust coating and so on.

General high pressure pressure corresponding to the saturation temperature   condenser outlet water

temperature, when the temperature difference is greater than 3--5 degrees need to clean the condenser. We do not recommend frequent chemical cleaning of the condenser to prevent corrosion of the condenser perforation leakage of fluorine, so it is very important to keep the circulating water clean and softened.

However, when the condenser must be cleaned, a professional water treatment expert should be found for analysis.

  • Unit parameter setting

1. The chilled water temperature is generally set at 7 degrees. (Anti-freezing protection is set to 4 degrees, when the weather is cool and the indoor load is too low, the water temperature may drop too fast and the machine has no time to stop the anti-freezing protection, then the water temperature can be set to 9 degrees).

2, summer indoor load is too high when the boot may appear compressor overload failure. (At this time, the refrigerated pump should be turned off to reduce the water flow, and the water valve should be fully opened when the water temperature is below 15 degrees. Prevent high pressure or overload failure due to excessive load and low pressure for a long time).

3, the cooling water temperature is best not higher than 40 degrees can not be lower than 25 degrees. (When the weather is cool, the cooling water valve can be turned off to keep the cooling water above 25 degrees)

4. Machine operation data must be recorded. Before starting, should check the power supply voltage phase imbalance can not be greater than 2%. When the pressure is less than 5kg,  it is not allowed to start, and then the machine may leak fluorine to prevent the system water from burning the compressor when it is started.

Five, common troubleshooting

  • Solenoid valve failure
Fault phenomenonreasonTrouble shooting
Closing action time exceeds 3 secondsThe small hole on the side of the valve plug is blockedEliminate dirt inside the small hole and install a filter in front of the valve
The valve does not open after the power is turned on1. The power supply voltage is below 85%Adjust the power supply voltage within ± 10% range
Coil burnt out or connector detached If necessary, use a manual device to open the valve for maintenance or replace the coil. The newly wound coil must be soaked and dried, anda layer of quartz powder and asphalt (weight to weight ratio 3:1) composite adhesive should be soaked between the coil and the shell
The gap between the valve  plug and the valve seat is not  sealed, and there is leakageThe small pores on the side of the valve plug are blocked, making it difficult to transmit medium pressure Eliminate dirt from small holes
The seal on the valve plug is damaged, worn or deformedReplace the sealing ring
 The pressure difference between the front and rear of the valve is less than 10% of the standard pressure valueComply with the regulations  on the front and rear pressure difference in the product manual
The static and dynamic sealingpoints of the valve body are not sealedThe sealing gasket is not placed correctlyPlace the sealing gasket correctly and tighten it evenly and reliably
Sealing gasket deformation, wear or decayReplace the seal
The valve plug does not start after being powered onThere is dirt inside the pressure relief holeEliminate dirt inside the pressure relief hole
Inappropriate control medium, i.e. viscosity too lowThe viscosity of the medium is low, and the pressure relief hole should be appropriately increased
  • The compressor is faulty
Fault phenomenonreasonTroubleshooting
 The compressor cannot startThe main switch failed to closeClose the switch
The fuse is blown and the  circuit switch is not closedCheck whether the circuit and motor winding are short circuited or grounded,  whether there is overload (after troubleshooting), replace the fuse or close the switch, and check whether the connection is loose or corroded
Thermal overload protection disconnectedOverload protection automatically resets, and the fault is eliminated before the thermal overload protection is restored to safety
Contactor or electromagnetic coil malfunctionRepair or replace
Shutdown due to safety device protectionDetermine the type and cause of the shutdown, and troubleshoot the issue before restoring the safety switch
No heat loadWaiting for heat load
 Repair or replace the electromagnetic coil
 Check if the motor has any  open circuit, short circuit or burnt out
 Check all wire connectors and tighten the wire terminal bolts
 Reset the safety switch
 The compressor cannot operate but makes noiseWiring errorCheck and rewire
Low VoltageCheck the power supply voltage
Starter failurereplace
Compressor damagereplace
The compressor has abnormal noise and vibrationA large amount of refrigerant  enters the compressorCheck the setting of the expansion valve
Compressor damagereplace
The compressor cannot increase or decrease the loadEnergy control malfunctionreplace
The load shedding device has malfunctionedreplace
Temperature controller level malfunction or wire  disconnectionreplace
Unreasonable level settingRESET
The interval between increasing and decreasing the load of the compressor is too shortAbnormal water temperature controllerreplace
Insufficient water flowAdjust water flow rate
 Compressor thermal protection switch disconnectedOperating conditions exceed the design rangeImprove conditions to keep operating conditions within acceptable limits
The exhaust valve is not fully openOpen the valve
motor faultReplace the compressor
  • The motor overload relay is disconnected
ReasonTroubleshooting
Voltage too low under high load conditionsCheck if the voltage drop of the power supply is too large
Motor winding damageReplace the compressor
Loose power cordCheck all connections and tighten them tightly
The condensation temperature is too highRefer to the method for handling high exhaust pressure
Voltage imbalance caused by power line failureCheck the power supply voltage, notify the  power supply bureau, and do not start the compressor until the fault is resolved
Overload relay broken, high ambient temperatureImprove ventilation to increase heat dissipation
  • The unit is faulty
Fault phenomenonreasonTroubleshooting
     Exhaust pressure too high There are non condensable gases in the systemDischarge non condensable gases
 Excessive refrigerant chargeExtract excess refrigerant
 The exhaust shut-off valve is not openOpen the exhaust shut-off valve
 The outlet temperature of the condenser is too highCheck if the installation of the unit is appropriate and if the fins are scaled
       Exhaust pressure too lowImproper adjustment of condensation temperatureCheck the control and operation process of the condenser
The suction shut-off valve is not fully openOpen the suction shut-off valve
Insufficient refrigerant Leak detection, repair and refrigerant filling
Low suction pressureRefer to the correct steps for handling low suction pressure below
  Refer to the following methods for handling compressor overload failure
      Abnormal fuel supplyOil filter inlet blockage clean
Liquid refrigerant enters the oil fraction Check the electric heater, adjust the expansion valve to increase superheat, check the liquid supply solenoid valve, and adjust the water flow rate
The oil pressure gauge is inaccurate Repair or replace, close the valve and only open it when there is a reading
Low oil levelcome on

END!